89x71.5mm
N.A.
N.A.
N.A.
N.A.
V, I,Hz: 0.5% F.S.
≤200ppm/°C
Response time:≤300ms
1-phase
100VAC, 500VAC, 60mVDC, 10VDC
200VDC
1AAC, 5AAC, 1ADC
N.A.
All
STD
VAC,VDC,AAC,ADC,
Hz (45-55Hz, 55-65Hz, 350-450Hz)
N.A.
N.A.
N.A.
0-20, 4-20mA; ±1V, 0-10V
N.A.
N.A.
Current or voltage input in the same
transducer.Field adjustment from 50
to 130% of the A/V input
24VAC, 48VAC, 115VAC,230VAC
CE
IP40
Housing (H x W)
Display type
Variables on display
Instantaneous variables
Energy variables
Accuracy
Temperature drift
Sampling rate
System type
Voltage inputs (Un)
Current inputs (In)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
Compact Transducer CVT DIN
CVT DIN is a series of compact and simple transducers for
the measurement of voltage, current and frequency. In a
module which is 71.5 mm wide, suitable for DIN rail
mounting, it offers three basic hardwares to measure: AC
voltage and current; DC voltage and current; frequency.
The current and voltage models allow to adjust the
transducer calibration from 50 to 130 % of the rated inputs
simply using a digital multimeter set on the resistance
measurement.
CVT DIN
Hardware Functions
In-Out
Performances
The best to suit your needs!
Comm
Input Formula Example
5AAC Radj=5000/ Ain (A) Ain=6A Radj=2500Ω
500VAC Radj=1500000/ Vin (V) Vin=250V Radj=6000Ω
1AAC R
adj=3000/ Ain
(A)
A
in=0.9A Radj
=3333Ω
100VAC Radj=30000/ Vin (V) Vin=80V Radj=3750Ω
1ADC Radj=3000/ Ain (A) Ain=0.9A Radj=3333Ω
200VDC R
adj=600000/ Vin (V)
V
in=190V Radj=3157Ω
60mVDC Radj=180000/ Vin (V) Vin=35mV Radj=5142Ω
10VDC Radj=30000/ Vin (V) Vin=6V Radj=5000Ω
33