Hardware Functions
In-Out
Performances
The best to suit your needs!
96x96x140mm
LCD (back lighted)
YES
4x3 1/2 DGT
7 1/2 DGT
V
LN
-A: ±(0.5% RDG+1DGT)
W-VA: ±(1% RDG+1DGT)
Class 1 (EN61036)
Class 2 (EN61268)
≤200ppm/°C
1.5 samples/s
Bal.: 3-phase, Unbal.:3-phase
57/100VAC, 120/208VAC, 230/400VAC,
380/660VAC
5A
3 for time period management
1 for program lock
Prog.: CT up to 5000A, VT up to 20kV
TRMS method
Sys:V
LN,VLL,VA,W,Wdmd,VAdmd, var, PF, Hz,
total varh,partial Wh, partial varh,gas,
H2O. Single-phase:VLN,A,VA,W,var,PF.
N.A.
Up to 2 (open collector or relay)
Up to 2 (relay or open collector)
N.A.
RS485 (Modbus), RS232
Action: on variables and outputs
Modular concept, plug-in modules,
phase asymmetry control, energy time
period management
24, 48, 115,230VAC
18 to 60V AC/DC, 90 to 260VAC/DC
CE, cURus, cCSAus
IP65
Housing (H x W x D)
Display type
Variables on display
Instantaneous variables
Energy variables
Accuracy
Temperature drift
Sampling rate
System type
Voltage inputs (Un)
Current inputs (In)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
WM24 96 is a modular universal utility meter that allows the
operator to continuously monitor the mains and measure
energy, gas and water by total or partial metering. All meas-
urements with a direct connection up to 830VAC (phase-
phase), up to 20kV (VT connection) and up to 5.000A (CT
connection) allow the operator to use WM24 96 in all the
light and medium industry applications. This universal utili-
ty meter has a standard IP65 protection degree and the
metering of energy is in compliance with class 1 “EN61036”
and class 2 “EN61268”.
WM24 96 is capable to measure and control, by means of
the two optional alarm outputs, all the main variables and
the maximum demanded power.
It is able to measure and display the total energies in the
four quadrants (+kvar-L, -kvar-L, +kvar-C, -kvar-C). The
access to the programming parameters can be locked in
order to avoid undesired modifications.
Furthermore the measured energies can be managed by
time period/tariff: t1-t2-t3-t4 by means of two input con-
tacts. Those contacts can be used, in alternative, as count-
er inputs to measure m
3
of gas and water.
Comm
Universal Utility Meter WM24 96
WM24 96
24