CARLO GAVAZZI MDI 40 TF - CONFIGURATION SOFTWARE Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Měření, testování a kontrola CARLO GAVAZZI MDI 40 TF - CONFIGURATION SOFTWARE. - Carlo Gavazzi Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 27
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
ENGLISH
MDI40
OPERATING INSTRUCTIONS
• General Features 2
• Technical Features 3
• Installation 9
• Preliminary Operations 11
• Front Panel Description 12
• Operating mode 15
Important:
We suggest you keep the original packing for a further
shipping of the instrument.
In order to guarantee a correct use of the instrument, we
recommend the user to carefully read the present instruc-
tion manual.
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]
Zobrazit stránku 0
1 2 3 4 5 6 ... 26 27

Shrnutí obsahu

Strany 1 - OPERATING INSTRUCTIONS

ENGLISHMDI40OPERATING INSTRUCTIONS• General Features 2• Technical Features 3• Installation 9• Preliminary Operations 11• Front Panel Description 12• O

Strany 2

10ENGLISHINSTALLATIONOverall dimensions and panel cut-out92 mm45 mm124 mmFSal1al296 mm48 mm91 mm112 mmmax. 10 mmMountingInsert the instrument into th

Strany 3 - Ω TEMPERATURE)

11ENGLISHConnectionsIn order to select the desired range (MDI 40V and MDI40A), jumper, ifnecessary, between the relevant screw terminals.Connect MDI 4

Strany 4

12ENGLISHConnection of the signal transmitters (in the models MDI40V and MDI40A):• 2 wires: signal to the measuring input; power supply to terminal 6;

Strany 5

13ENGLISHFRONT PANEL DESCRIPTIONFSCARLO GAVAZZIal1al21. Key-pad:functions available outside the programming phase.Key to be pressed: Displaying of se

Strany 6

14ENGLISHF + For longer than 2 seconds: maximum reset of themeasured value (the display will be blinking);F + For longer than 2 seconds: minimum

Strany 7

15ENGLISHF In the menus: exit from the programming phase (message “End“on the display) and return to the measuring and control function; In theseconda

Strany 8

16ENGLISHOPERATING MODE• Power-onWhen you switch the unit on, the instrument shows for approximately 5seconds the instruments’s software revision, for

Strany 9

17ENGLISHpassword is not correct, the display shows “End” and the instrumentgoes back to the measuring and control phase.PROGRAMMING OF A NEW PASSWORD

Strany 10

18ENGLISHof MDI40 indicating the position of the current function with regardsto the others. The flow chart also makes more easily understandablethe c

Strany 11

19ENGLISHNOTE: if the measured variable goes beyond the scale limits “Lo.E”/”Hi.E”, the value displayed during the measuring phase will be blinkingan

Strany 12

2ENGLISHCARLO GAVAZZI InstrumentsMulti-range µP-based panel indicators/controllers for voltage, cur-rent and temperature measurementsMDI40.V / MDI40.A

Strany 13 - CARLO GAVAZZI

20ENGLISHaccording to the following relationship: °F = (1.8 x °C) + 32.Example: “Lo.E”=-50°C ⇒ “Lo”=-58°F; “Hi.E”=+760°C ⇒ “Hi”=+1400°F,means that t

Strany 14

21ENGLISH do.L : down/low alarm set-point with latch function. The alarm func-tions as per “do” and can be reset only manually when the F

Strany 15

22ENGLISHNOTE: the hysteresis is to be programmed according to the displayedrange. oF.d : value expressed in seconds of the time delay at the alarm se

Strany 16

23ENGLISHmeasurement of a process signal from a transmitter: 0 to 20mA, 4 to20mA, 0 to 10V, 0 to 5V, 1 to 5V and so on which can correspond to apress

Strany 17

24ENGLISHis to be entered making various attempts starting from a minimum value,for example “Fi.C”=3. The datum will not remain stable, therefore “Fi

Strany 18

25ENGLISH“Hi.A” (%) = 100 x ?V that in our example corresponds to: 10100 x 5V/10 = 50%, therefore enter 50.00.Also in this case, as per the elect

Strany 19

26ENGLISHAlarm status following sensor's breakage.TCStatus oFF do uP d.do uP.L do.LOpening on oFF on oFF** on* oFF*Short-circuit //////* Depend

Strany 20

27ENGLISHGross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]

Strany 21

3ENGLISH• programming of the scales: electrical scale, displayed scale anddecimal point position;• programming of all the parameters relating to the

Strany 22

4ENGLISHTEMPERATURE DRIFT (CURRENT)DC / AC measurement: ± 200 ppm/°CTEMPERATURE DRIFT (RTD / TC / Ω)± 200 ppm/°CSAMPLING RATEV/A measurement: 4 times/

Strany 23

5ENGLISHINPUTS (CURRENT)2 mA, range: -1.999 mADC / 0 mAAC to 1.999 mA20 mA, range: -19.99 mADC / 0 mAAC to 19.99 mA200 mA (on request), range: -199.9

Strany 24

6ENGLISHCOMPENSATION (TC)Cold junction, within a temperature range from 0 to 50°C of ambienttemperature.ALARM SET-POINTS2 independent standard set-poi

Strany 25

7ENGLISHANALOGUE RETRANSMISSION (ON REQUEST)From 0 to 20 mADC / from 0 to 10 VDC, programmable within the wholerange of retransmission;Accuracy and r

Strany 26

8ENGLISHEXCITATION OUTPUT15 VDC insulated, not stabilized / max. 40 mA;20 VDC/20mA typical (@ rated value of power supply input).For MDI40C the power

Strany 27

9ENGLISHCMRR: 100 dB, from 40 to 60 HzEMC: IEC 801-2, IEC 801-3, IEC 801-4 (level 3)IN ACCORDANCE WITH THE FOLLOWING STANDARDSEN 61010-1, IEC 1010-1,

Komentáře k této Příručce

Žádné komentáře