CARLO GAVAZZI
CONTROLS
SERIAL COMMUNICATION PROTOCOL
WM4-96
V1 R3
Page
3.1.28 MAX and MIN type coding
MAX and MIN type Selection
XXXXXXXX XX000000 variable field (from 000000 to 110100, see TABLE 3.1.1)
0101XXXX XXXXXXXX bit check
3.2 EVENT LOGGING
Event logging map
2300 4 words
Event 1
2308 4 words
Event 2
2310 4 words
Event 3
2318 4 words
Event 4
2320 4 words
Event 5
2328 4 words
Event 6
31F8 4 words
Event 480
The stored information relevant to every event are the following: event type, hour, minutes, seconds,
day, month, year, value.
All these data are included in the relevant 4 words, coded as follow.
To reset the events, it is necessary to write 0 in every of the sideways listed addresses and to reset
the event counter, placed at the address 80Ch.
N
th
event coding
hour min event type
Word1 XXXXX XXXXXX XXXXX
month day year
Word2 XXXX XXXXX XXXXXXX
Seconds variable type
Word3 0101XXXXXX
XXXXXX
value
Word4 XXXXXXXXXXXXXXXX
Variable type coding:
Refer to the relevant table in paragraph 3.1.1.