ENGLISH
NOTE: the hysteresis is to be programmed according to the displayed
range.
oF.d : value expressed in seconds of the time delay at the alarm set-
points deactivation (OFF).
Value to be programmed within the range:0 < oF.d < 255.
This delay can be useful when it is necessary to guarantee the alarm
output activation for a sufficiently long time which is to be acquired by the
processing system connected downstream MDI40.
on.d : value expressed in seconds of the time delay at the alarm set-
points activation (ON). This value is to be programmed within the range:
0 < on.d < 255.
This value can be useful when it is necessary to avoid the alarm set-
points activation if the alarm duration is not long enough. Example: when
the pressure to be measured decreases very quickly because of air
bubbles, but this is not a danger for the monitored plant.
RLY : normal status of the relay coil.
nd : normally de-energized coil.
nE : normally energized coil.
FiL : menu to program the digital filters parameters.
This function allows you to solve two different kinds of problems:
stabilize the value of the instantaneous measurement displayed by
MDI40 when the value is not enough stable from the beginning and will
not therefore allow either a clear reading on the display or a good control
by the alarm set-points;
allow an amplitude of the displayed scale as regards to the electrical
one >2.
An example of how the electrical scale is to be used can be the